Running Individual Tests
When to Use a Remote Unit
4
4-5
1. If you are using a DSP-100 main unit as the remote, turn the remote unit’s
rotary switch to SMART REMOTE. If you are using a smart remote unit, turn
its rotary switch to ON.
2. Use a 2m patch cable of the correct impedance to connect the remote to the far
end of the cable link.
3. On Model DSP-100, remove any cable connected to the test tool’s BNC
connector.
4. Turn the rotary switch on the main unit to SINGLE TEST.
5. Use a 2m patch cable of the correct impedance to connect the test tool to the
near end of the cable link. On Model DSP-2000, connect to the CABLE TEST
jack.
6. Use U D to highlight the test you want to run.
7. Press E to start the highlighted test.
Note
If a remote is required for the test, but is not connected, the test tool
displays the message SCANNING FOR REMOTE and does not
run the test until a remote is connected.
If the calibration message appears, refer to “Calibrating the Test
Tool” in Chapter 6 for complete calibration instructions.